An experimental study of a novel integrated desiccant air conditioning system for building applications

Abstract To date, the application of liquid desiccant air conditioning systems in built environment applications, particularly small scale, has been limited. This is primarily due to large system size and complexity, issues of desiccant solution leakage and carry-over and equipment corrosion. As a result, a novel integrated desiccant air conditioning system (IDCS) has been developed. The system combines the regenerator, dehumidifier and evaporative inter-cooler into a single membrane based heat and mass exchanger. This paper presents an evaluation, based on experimental data, of the novel IDCS operating with a potassium formate (CHKO2) desiccant working fluid. A range of tests have been completed to characterise the performance of the dehumidifier, regenerator and complete IDCS. Cooling output in the range of 570 to 1362 W and dehumidifier effectiveness in the range of 30 to 47% are presented. An issue encountered has been an imbalance between moisture removal rate in the dehumidifier and moisture addition rate in the regenerator. As a result, an adjusted thermal COP (COPth,adj) value has been calculated. COPth,adj values of 1.26 have been achieved with an average of 0.72. Electrical COP (COPel) values of 3.67 have been achieved with an average of 2.5. The work demonstrates that the novel IDCS concept is viable and has provided progress to the field of liquid desiccant air conditioning technology for building applications. Further work is required in order to address the main issue of mass imbalance between the dehumidifier and regenerator.

[1]  Clive B. Beggs,et al.  The use of solar desiccant cooling in the UK: a feasibility study , 2002 .

[2]  Luis Pérez-Lombard,et al.  A review on buildings energy consumption information , 2008 .

[3]  Å. Melinder Thermophysical Properties of Aqueous Solutions Used as Secondary Working Fluids , 2007 .

[4]  Ursula Eicker,et al.  Experimental performance analysis and modelling of liquid desiccant cooling systems for air conditioning in residential buildings , 2006 .

[5]  Li-Zhi Zhang,et al.  Energy performance of independent air dehumidification systems with energy recovery measures , 2005, Energy.

[6]  Abdulmajeed A. Mohamad,et al.  A review on solar cold production through absorption technology , 2012 .

[7]  Marco Beccali,et al.  Energy performance evaluation of a demo solar desiccant cooling system with heat recovery for the regeneration of the adsorption material , 2012 .

[8]  Mark D. Semon,et al.  POSTUSE REVIEW: An Introduction to Error Analysis: The Study of Uncertainties in Physical Measurements , 1982 .

[9]  K. F. Fong,et al.  Comparative study of different solar cooling systems for buildings in subtropical city , 2010 .

[10]  Pradeep Bansal,et al.  Performance analysis of liquid desiccant dehumidification systems , 2007 .

[11]  Gershon Grossman,et al.  Experimental investigation of a liquid desiccant system for solar cooling and dehumidification , 2007 .

[12]  G. Longo,et al.  Experimental and theoretical analysis of heat and mass transfer in a packed column dehumidifier/regenerator with liquid desiccant , 2005 .

[13]  S. Chungpaibulpatana,et al.  A review of absorption refrigeration technologies , 2001 .

[14]  Ala Hasan,et al.  Indirect evaporative cooling : Past, present and future potentials , 2012 .

[15]  Andrew Lowenstein,et al.  Review of Liquid Desiccant Technology for HVAC Applications , 2008 .

[16]  S. Jain,et al.  Experimental performance of a liquid desiccant dehumidification system under tropical climates , 2011 .

[17]  V. I. Hanby,et al.  A probabilistic analysis of the future potential of evaporative cooling systems in a temperate clima , 2011 .

[18]  Eric Kozubal,et al.  Desiccant Enhanced Evaporative Air-Conditioning (DEVap): Evaluation of a New Concept in Ultra Efficient Air Conditioning , 2011 .