Detection of brushless exciter rotating diodes failures by spectral analysis of main output voltage

Rotating rectifier is a basic part of synchronous generators. Inappropriate operation of this component can prove costly for the machine's owner. This paper presents theoretical analysis and experimental validation for detecting failure of brushless exciter rotating diodes that can fail either open circuit or short circuit. Harmonic analysis of the alternator output voltage waveform is performed when machine is unloaded as well as when it runs around its rated load. Apparition of characteristic frequencies can be useful to distinguish the rotating diodes state. By considering the relative amplitudes at specific harmonics, it is possible to discriminate short circuit diode failure case from open circuit diode breakdown.

[1]  Abolfazl Vahedi,et al.  Improved dynamic average modelling of brushless excitation system in all rectification modes , 2010 .

[2]  Mosad M. El Missiry Excitation Control of a Brushless Synchronous Motor , 1984, IEEE Transactions on Industry Applications.

[3]  K. Veszpremi,et al.  Optimal operation of the rotating transformer brushless excitation of synchronous machine , 2003, 2003 IEEE International Symposium on Industrial Electronics ( Cat. No.03TH8692).

[4]  Shen Feng,et al.  Study of brushless excitation system parameters estimation based on improved genetic algorithm , 2008, 2008 Third International Conference on Electric Utility Deregulation and Restructuring and Power Technologies.

[5]  Chao Zhang,et al.  Simulation of harmonic armature reaction in synchronous brushless excitation , 2011, 2011 2nd International Conference on Artificial Intelligence, Management Science and Electronic Commerce (AIMSEC).

[6]  F.C. Trutt,et al.  Condition monitoring of brushless three-phase synchronous generators with stator winding or rotor circuit deterioration , 2001, Conference Record of the 2001 IEEE Industry Applications Conference. 36th IAS Annual Meeting (Cat. No.01CH37248).

[7]  Chang Xu,et al.  A neural network based approach for the detection of faults in the brushless excitation of a synchronous motor , 2009, 2009 IEEE International Conference on Electro/Information Technology.

[8]  D.J. Morrow,et al.  Noninvasive detection of brushless exciter rotating diode failure , 2004, IEEE Transactions on Energy Conversion.

[9]  M. Poloujadoff,et al.  Modeling of polyphase brushless exciter behavior for failing diode operation , 1998 .

[10]  Woonki Na A feedforward controller for a brushless excitation system during the diode open circuit fault operation , 2011, 2011 IEEE Power and Energy Society General Meeting.

[11]  Juha Pyrhonen,et al.  Modelling the brushless excitation system for a synchronous machine , 2009 .

[12]  Aaron Cramer,et al.  Synchronous Machine Model With Voltage-Behind-Reactance Formulation of Stator and Field Windings , 2012, IEEE Transactions on Energy Conversion.

[13]  T. D. Batzel,et al.  Predictive diagnostics for the main field winding and rotating rectifier assembly in the brushless synchronous generator , 2003, 4th IEEE International Symposium on Diagnostics for Electric Machines, Power Electronics and Drives, 2003. SDEMPED 2003..